H05VV-F

Home » Kabel Metal » Low Voltage » H05VV-F

H05VVF 300/500V
CU/PVC/PVC
Standard Specification : IEC 60227-6:2001 (IEC 71c)
Flexible Copper Conductor, PVC Insulated, PVC Sheathed

Application:  
• Power Cord or internal wiring with medium mechanical stress for electrical equipment, 
  machineries, luminaires and other portable appliances in dry indoor premises and outdoor 
  application.
• Permanent exposed wiring in humid environment, installation in tray or under plaster
  for industrial three phase 380-415 VAC or single phase 220-240 VAC multipurpose application,
  inherently flame retardant in compliance with IEC 60332-1
 
Electrical Data
Cable Size (No. of core x conductor Area)Conductor make- up (No.0f wire x Diameter)DC Resistance atCurrent-Carrying Capacity in 30oCShort circuit current at 1 secInsulation/Sheath ThicknessOverall DiameterCable weightStandard Packing Lenght *
20oC Conductor70oC Insulation
nom.Max.Max.
nom.Max.Max.nom.approxapprox
(mm2)(mm)(ohm/km)(Mohm.km)(A)(kA)(mm)(mm)(kg/km)(meter/packing)
2 x0.75 24x0.20 26.0 0.011 6 86 0.6/0.8 6.2 57 100/c
2 x1.0 32x0.20 19.5 0.010 10 115 0.6/0.8 6.8 70 100/c
2 x1.5 30x0.25 13.3 0.010 15 173 0.7/0.8 7.9 94 100/c
2 x2.5 50x0.25 7.98 0.009 20 288 0.8/1.0 9.8 146 100/c
2 x4 56x0.30 4.95 0.008 26 460 0.8/1.1 10.9 198 100/c
2 x6 84x0.30 3.30 0.007 33 690 0.8/1.2 12.3 264 1000/d
2 x10 80x0.40 1.91 0.006 45 1150 1.0/1.3 15.3 421 1000/d
                   
3 x0.75 24x0.20 26.0 0.011 6 86 0.6/0.8 6.5 69 100/c
3 x1.0 32x0.20 19.5 0.010 10 115 0.6/0.8 7.2 84 100/c
3 x1.5 30x0.25 13.3 0.010 15 173 0.7/0.9 8.6 118 100/c
3 x2.5 50x0.25 7.98 0.009 20 288 0.8/1.1 10.6 182 100/c
3 x4 56x0.30 4.95 0.008 26 460 0.8/1.1 11.6 244 100/c
3 x6 84x0.30 3.30 0.007 33 690 0.8/1.2 13.1 331 1000/d
3 x10 80x0.40 1.91 0.006 45 1150 1.0/1.4 16.5 538 1000/d
3x16 126x0.40 1.21 0.005 61 1840 1.0/1.4 19.5 733 1000/d
3x25 196x0.40 0.780 0.005 80 2875 1.2/1.5 23.5 1102 1000/d
3x35 276x0.40 0.554 0.004 98 4025 1.2/1.6 26.0 1471 1000/d
3x50 396x0.40 0.386 0.004 122 5750 1.4/1.7 30.5 2072 1000/d
3x70 360x0.50 0.272 0.004 152 8050 1.4/1.8 35.0 2814 1000/d
                   
4 x0.75 24x0.20 26.0 0.011 6 86 0.6/0.8 7.1 84 100/c
4 x1.0 32x0.20 19.5 0.010 10 115 0.6/0.9 8.1 107 100/c
4 x1.5 30x0.25 13.3 0.010 15 173 0.7/1.0 9.6 149 100/c
4 x2.5 50x0.25 7.98 0.009 20 288 0.8/1.1 11.6 225 100/c
4 x4 56x0.30 4.95 0.008 26 460 0.8/1.2 12.9 311 1000/d
4 x6 84x0.30 3.30 0.007 33 690 0.8/1.3 14.6 421 1000/d
4 x10 80x0.40 1.91 0.006 45 1150 1.0/1.4 18.1 677 1000/d
4x16 126x0.40 1.21 0.005 61 1840 1.0/1.5 21.5 927 1000/d
4x25 196x0.40 0.780 0.005 80 2875 1.2/1.6 26.0 1396 1000/d
4x35 276x0.40 0.554 0.004 98 4025 1.2/1.7 29.0 1867 1000/d
4x50 396x0.40 0.386 0.004 122 5750 1.4/1.8 34.0 2633 1000/d
4x70 360x0.50 0.272 0.004 152 8050 1.4/1.9 39.0 3584 1000/d
                   
5 x0.75 24x0.20 26.0 0.011 4 86 0.6/0.9 8.0 105 100/c
5 x1.0 32x0.20 19.5 0.010 8 115 0.6/0.9 8.9 129 100/c
5 x1.5 30x0.25 13.3 0.010 11 173 0.7/1.1 10.7 185 100/c
5 x2.5 50x0.25 7.98 0.009 15 288 0.8/1.2 12.9 279 1000/d
5 x4 56x0.30 4.95 0.008 20 460 0.8/1.3 14.4 385 1000/d
5 x6 84x0.30 3.30 0.007 25 690 0.8/1.4 16.2 521 1000/d
5 x10 80x0.40 1.91 0.006 34 1150 1.0/1.5 20.1 838 1000/d
Test Voltage : 2,000 VAC/5 minutes, except for insulation thickness less than 0.7 mm (1,500 VAC/5 minutes)
* c = coil      d = drum